Galvanic Isolators, suitable for your hazardous area needs. Includes a range from ATEX & IECEx certifications, suitable for zones 2, (0, 1, 2, 20 & 21)

MTL 5511 SWITCH/PROXIMITY DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2, (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Repeater power supply 4/20mA, HART®, 2- or 3-wire transmitters
  • Number of channels: One
  • Safe-area output: Signal range: 4 to 20mA. Under/over-range: 0 to 24mA
  • Hazardous-area input: Signal range: 0 to 24mA (including over-range)
  • Transmitter voltage: 16.5V at 20mA
  • Maximum current consumption (with 20mA signal) - 51mA at 24V
  • Power dissipation within unit (with 20mA signal): MTLx541 0.7W @ 24V dc.
  • MTLx541S 1.0W @ 24V dc

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5516C SWITCH/ PROXIMITY DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Switch/ Proximity Detector Interface
  • Number of channels: 2, with line fault detection
  • Hazardous-area inputs: Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
  • Voltage applied to sensor: 7 to 9V dc from 1kOhms ±10%
  • Maximum current consumption: 35mA at 24V
  • Power dissipation within unit: 0.84W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5525 SOLENOID/ALARM DRIVER
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Solenoid/Alarm Driver, switch operated with override, IIC, low power
  • Number of channels: One
  • Hazardous-area output:
  • Minimum output voltage: 7V at 48mA
  • Maximum output voltage: 24V from 300Ohms
  • Current limit: 48mA
  • Maximum current consumption: 100mA at 24V dc
  • Power dissipation within unit:
  • 1.3W with typical solenoid valve, output on
  • 1.9W worst case

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5561 FIRE AND SMOKE DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (, 0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Fire and Smoke Detector Interface
  • Number of channels: Two, fully floating, loop powered.
  • Input voltage: 6 to 30V dc
  • Current range: 1 to 40mA, nominal
  • Maximum output voltage: 28V from 300Ohms
  • Power dissipation within unit:
  • 0.7W maximum at 24V with 40mA signal (each channel)
  • 0.9W maximum at 30V with 40mA signal (each channel)

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5544 REPEATER POWER SUPPLY
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Repeater Power Supply, 4/20mA, HART®, 2- or 3- wire transmitters
  • Number of channels: Two
  • Safe-area output: Signal range: 4 to 20mA. Under/over-range: 0 to 24mA
  • Hazardous-area input: Signal range: 0 to 24mA (including over-range)
  • Transmitter voltage: 16.5V at 20mA
  • Maximum current consumption (with 20mA signals) 96mA at 24V dc
  • Power dissipation within unit (with 20mA signals): MTLx544 1.4W @ 24V dc
  • MTLx544S 1.9W @ 24V dc

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5541 REPEATER POWER SUPPLY
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I



ATEX, IECEx
  • Switch/ ProximityDetector Interface
  • Number of channels: One
  • Hazardous-area inputs
  • Inputs conforming to BS EN60947–5–6:2001 standards for
  • proximity detectors (NAMUR)
  • Voltage applied to sensor: 7 to 9V dc from 1kOhms ±10%
  • Maximum current consumption: 25mA at 24V
  • Power dissipation within unit: 0.6W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5514 SWITCH/ PROXIMITY DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Switch/ Proximity Detector Interface
  • Number of channels: One
  • Hazardous–area inputs
  • Inputs conforming to BS EN60947–5–6:2001 standards for
  • proximity detectors (NAMUR)
  • Voltage applied to sensor: 7 to 9V dc from 1kOhms ±10%
  • Maximum current consumption: 25mA at 24V dc
  • Power dissipation within unit: 0.6W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5521 SOLENOID/ALARM DRIVER
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex I (M1) [Ex ia Ma] I

ATEX, IECEx
  • Solenoid/ Alarm Driver, loop-powered, IIC
  • Number of channels: One
  • Hazardous-area output: (MTLx521)
  • Minimum output voltage: 12.8V at 48mA
  • Maximum output voltage: 24V from 180Ohms
  • Current limit: 48mA
  • Maximum current consumption: 90mA at 24V
  • Power dissipation within unit:1.4W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5544D REPEATER POWER SUPPLY
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex I (M1) [Ex ia Ma] I
ATEX, IECEx
  • Repeater Power Supply
  • single channel, 4/20mA, HART®, 2- or 3-wire transmitters, two outputs
  • Number of channels: One
  • Safe-area output: Signal range: 4 to 20mAUnder/over-range: 0 to 24mA
  • Hazardous-area input: Signal range: 0 to 24mA (including over-range)
  • Transmitter voltage: 16.5V at 20mA
  • Maximum current consumption: (with 20mA signals) 96mA at 24V dc
  • Power dissipation within unit: (with 20mA signals) 1.4W @ 24V dc

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4511 SWITCH/PROXIMITY DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Repeater power supply 4/20mA, HART®, 2- or 3-wire transmitters
  • Number of channels: One
  • Safe-area output: Signal range: 4 to 20mA. Under/over-range: 0 to 24mA
  • Hazardous-area input: Signal range: 0 to 24mA (including over-range)
  • Transmitter voltage: 16.5V at 20mA
  • Maximum current consumption (with 20mA signal) - 51mA at 24V
  • Power dissipation within unit (with 20mA signal): MTLx541 0.7W @ 24V dc.
  • MTLx541S 1.0W @ 24V dc

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4561 FIRE AND SMOKE DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Fire and Smoke Detector Interface
  • Number of channels: Two, fully floating, loop powered.
  • Input voltage: 6 to 30V dc
  • Current range: 1 to 40mA, nominal
  • Maximum output voltage: 28V from 300Ohms
  • Power dissipation within unit:
  • 0.7W maximum at 24V with 40mA signal (each channel)
  • 0.9W maximum at 30V with 40mA signal (each channel)

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4516C SWITCH/ PROXIMITY DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Switch/ Proximity Detector Interface
  • Number of channels: 2, with line fault detection
  • Hazardous-area inputs: Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
  • Voltage applied to sensor: 7 to 9V dc from 1kOhms ±10%
  • Maximum current consumption: 35mA at 24V
  • Power dissipation within unit: 0.84W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4525 SOLENOID/ALARM DRIVER
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Solenoid/Alarm Driver, switch operated with override, IIC, low power
  • Number of channels: One
  • Hazardous-area output:
  • Minimum output voltage: 7V at 48mA
  • Maximum output voltage: 24V from 300Ohms
  • Current limit: 48mA
  • Maximum current consumption: 100mA at 24V dc
  • Power dissipation within unit:
  • 1.3W with typical solenoid valve, output on
  • 1.9W worst case

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4544 REPEATER POWER SUPPLY
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Repeater Power Supply, 4/20mA, HART®, 2- or 3- wire transmitters
  • Number of channels: Two
  • Safe-area output: Signal range: 4 to 20mA. Under/over-range: 0 to 24mA
  • Hazardous-area input: Signal range: 0 to 24mA (including over-range)
  • Transmitter voltage: 16.5V at 20mA
  • Maximum current consumption (with 20mA signals) 96mA at 24V dc
  • Power dissipation within unit (with 20mA signals): MTLx544 1.4W @ 24V dc
  • MTLx544S 1.9W @ 24V dc

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4541 REPEATER POWER SUPPLY
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I

ATEX, IECEx
  • Switch/ ProximityDetector Interface
  • Number of channels: One
  • Hazardous-area inputs
  • Inputs conforming to BS EN60947–5–6:2001 standards for
  • proximity detectors (NAMUR)
  • Voltage applied to sensor: 7 to 9V dc from 1kOhms ±10%
  • Maximum current consumption: 25mA at 24V
  • Power dissipation within unit: 0.6W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4514 SWITCH/ PROXIMITY DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Switch/ Proximity Detector Interface
  • Number of channels: One
  • Hazardous–area inputs
  • Inputs conforming to BS EN60947–5–6:2001 standards for
  • proximity detectors (NAMUR)
  • Voltage applied to sensor: 7 to 9V dc from 1kOhms ±10%
  • Maximum current consumption: 25mA at 24V dc
  • Power dissipation within unit: 0.6W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4521 SOLENOID/ALARM DRIVER
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex I (M1) [Ex ia Ma] I
ATEX
  • Solenoid/ Alarm Driver, loop-powered, IIC
  • Number of channels: One
  • Hazardous-area output: (MTLx521)
  • Minimum output voltage: 12.8V at 48mA
  • Maximum output voltage: 24V from 180Ohms
  • Current limit: 48mA
  • Maximum current consumption: 90mA at 24V
  • Power dissipation within unit:1.4W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4544D REPEATER POWER SUPPLY
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex I (M1) [Ex ia Ma] I
ATEX, IECEx
  • Repeater Power Supply
  • single channel, 4/20mA, HART®, 2- or 3-wire transmitters, two outputs
  • Number of channels: One
  • Safe-area output: Signal range: 4 to 20mAUnder/over-range: 0 to 24mA
  • Hazardous-area input: Signal range: 0 to 24mA (including over-range)
  • Transmitter voltage: 16.5V at 20mA
  • Maximum current consumption: (with 20mA signals) 96mA at 24V dc
  • Power dissipation within unit: (with 20mA signals) 1.4W @ 24V dc

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

PEPPERL+FUCHS KFD2-SR2-EX1.W
I.S. SWITCH AMPLIFIER
Zones: 0, 1, 2
[Eex ia] IIC [circuit(s) in zone 0/1/2]
(Eex nL) IIC X [circuit(s) in zone 2]
Eex nAC IIC T4 [device in zone 2]
ATEX
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • Relay contact output
  • Line fault detection (LFD)
  • Reversible mode of operation
  • Up to SIL2 acc. To IEC 61508

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

PEPPERL+FUCHS KFD2-CD2-EX2
I.S. CURRENT DRIVER
Zones: 0, 1, 2
[Eex ia] IIC (-20oC ? Tamb ? 60 °C) [circuit(s) in zone 0/1/2]
ATEX
  • 2-channel isolated barrier
  • 24 V DC supply (PowerRail)
  • Current output up to 700 ? load
  • I/P and valve positioners
  • Accuracy 0.05%
  • Up to SIL2 acc. To IEC 61508

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

PEPPERL+FUCHS KFD2-STC-EX1
I.S. SMART TRANSMITTER POWER SUPPLY
Zones: 0, 1, 2
[Eex ia] IIC, [Ex ia D] [circuit(s) in zone 0/1/2/20/21/22]
Ex nA II T4 X
ATEX
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • 2-wire SMART transmitters or current sources
  • Output 4 mA … 20 mA or 1 V … 5 V
  • Sink or source mode
  • Housing width 12.5mm
  • Up to SIL2 acc. To IEC 61508

Add to enquiry

Thank you, this has been added, click here to view your enquiry.