INTRINSICALLY SAFE -ZENER SAFETY BARRIERS &
ISOLATOR INTERFACE MODULES
|
|
MTL7700 SERIES
IS Zener Safety Barrier |
- Ambient temperature and humidity limits
–20 to +60°C continuous working
–40 to +80°C storage 5–95% RH
- Leakage current
For ‘basic’ barriers with a working voltage of 5V
or more, the leakage current decreases by at least one decade
per volt reduction in applied voltage below the working voltage,
over two decades. For the MTL7755ac/7756ac it decreases by at
least one decade for a 0.4V reduction in applied voltage.
- Terminations
Removable terminals accommodate conductors up to 2.5mm 2 (13AWG).
Hazardous-area terminals are identified by blue labels. Removal
force >15N
- Mounting and earthing By 35mm Top Hat DIN rail
|
- Colour coding of barrier label
Grey: non-polarised
Red: positive polarity (MTL7706 negative to transmitter ) Black:
negative polarity
White: dummy barrier, MTL7799
- Weight
140g approx
-
|
|
 |
Datasheet |
| Certificates available for different models by
request |
|
| |
|
|
|
- Resistant to humid and corrosive atmospheres
- - 40°C to +70°C ambient temperature range
- Operates on a variety of bus protocols
- Wide range of input or output types, in any mix
- 'Hot-swapping' of modules
- Automatic module addressing Self-diagnostics
- Self-contained - no additional hardware (e.g., DIN-rail terminals)
- 6mm per channel effective packing density
- Redundant LANs and power supplies
- HART® pass-through
Self-configuring-needed HART® pass-through
|
|
|
| |
Datasheets and certificates available for individual
components by request |
| |
|
|
MTL
8000 SERIES
Process I/O for Process Control |
|
|
MTL 4000 SERIES
IS Isolating Interface Module |
- ATEX EEx ia IIC
- Location of units
Safe area
- Terminals
Accommodate conductors of up to 2.5mm2 stranded or singlecore
- Isolation 250V rms between safe-area and hazardous-area
terminals tested
at 1500V rms min between safe and hazardous terminals
- Long term drift
No recalibration necessary
- Maximum safe-area voltage
Um = 250V rms or dc
- Hazardous-area connectors
SCC01: Screw-clamp connector accommodates conductors of 14AWG
max.CCH01: Crimp-contact header accommodates:CRC01 crimps for
conductors of 1420AWG, or
CRC02 crimps for conductors of 1824AWG
|
|
|
 |
Datasheet |
| Certificates available for different models by
request |
|
| |
| |
|
|
MTL5000 SERIES
IS Isolating Interface Module |
- ATEX EEx ia IIC
- Connectors Each unit is supplied with signal
and power connectors, as applicable. When using crimp ferrules
for the hazardous and non-hazardous (safe) signal connectors the
metal tube length should be 12mm and the wire trim length 14mm.
For the power connectors the metal tube length should be 10mm
and the wire trim length 12mm.See INM5000 for recommended ferrules.
- Isolation 250V rms between input, output and
power supply terminals, tested at 1500V rms minimum between safe-
and hazardous-area terminals. MTL5073, output and power supply
not isolated.
- Location of units
Safe area
- Terminals
Accommodate conductors of up to 2.5mm2 stranded or singlecore
|
- Mounting
On 35mm (top hat) rail to
EN 5002235 x 7.5; BS 5584;
35 x 27 x 7.3 DIN 46277
- Ambient temperature limits
-20 to +60deg C (-6 to +140deg F) operating
-40 to +80deg C (-40 to +176deg F) storage
- Humidity
5 to 95% relative humidity
- Weight
110g approx (except where indicated)
|
|
|
|
|
|
KFD2-SR2-Ex1.W
KFD2-SR2-Ex2.W
Isolated Switch Amplifier
|
- ATEX EEx ia IIC
- Type of protection [EEx nL]
- Explosion group IIA IIB IIC
- Voltage 10.5 V
- Current 13 mA
- Power 34 mW (linear characteristic)
- 1-channel
- Reversible mode of operation
- 1 relay output with 1 changeover contact
- EMC acc. to NAMUR NE 21
- LB/SC monitoring
- LB/SC collective error message via Power Rail
- SIL1 up to SIL3 acc. to IEC 61508
|
|
|
|
|
KFD2-PT-Ex1
IS Isolator for Potentiometer
|
- ATEX EEx ia IIC
- 1- channel
- 24 V DC nominal supply voltage
- Current or Voltage output
- Accuracy 0.05%EMC acc. to NAMUR NE 21
|
|
|
|
|
KFD2-SD-Ex1.36
IS Isolator Solenoid Driver
|
- ATEX EEx ia IIB
- 1- channel
- Installation permissable in zone 2
- Current limit 80 mA
- Usable up to SIL3 acc. to IEC 61508
- Application: Control/supply for intrinsically safe valves, audible alarms, indicators etc. Supply of semiconductor in place of evaluation or lead breakage. If semiconductors (eg LED or LCD-units) are controlled, a parallel resistance of approx 10 kOhm directly at the consumer may be necessary
|
|
|
|
|
KFD2-SD-Ex1.48
IS Isolator Solenoid Driver
|
- ATEX EEx ia IIC
- 1- channel
- Device installation permissable in zone 2
- 24 Volts DC nominal supply voltage
- Usable up to SIL 3 acc. to IEC 61508
- IP20
- Temperature -20...60C (253-333K)
- Mass 100g
|
|
| |